| Article number | 6ES7332-5RD00-0AB0 |
| SIMATIC S7,SM 332 ANALOG OUTPUT | |
| Supply voltage | |
| Load voltage L+ | |
|
● Rated value (DC)
|
24 V |
|
● Reverse polarity protection
|
Yes |
| Input current | |
| from load voltage L+ (without load), max. | 200 mA |
| from backplane bus 5 V DC, max. | 80 mA |
| Power loss | |
| Power loss, typ. | 4 W |
| Analog outputs | |
| Number of analog outputs | 4 |
| Voltage output, short-circuit protection | Yes |
| Voltage output, short-circuit current, max. | 70 mA |
| Current output, no-load voltage, max. | 14 V |
| Output ranges, current | |
|
● 0 to 20 mA
|
Yes |
|
● 4 mA to 20 mA
|
Yes |
| Load impedance (in rated range of output) | |
|
● with current outputs, max.
|
500 Ω |
| Cable length | |
|
● shielded, max.
|
200 m |
| Analog value generation for the outputs | |
| Integration and conversion time/resolution per channel | |
|
● Resolution with overrange (bit including sign), max.
|
15 bit |
| Errors/accuracies | |
| Operational error limit in overall temperature range | |
|
● Current, relative to output range, (+/-)
|
0.55 % |
| Basic error limit (operational limit at 25 °C) | |
|
● Current, relative to output range, (+/-)
|
0.2 % |
| Interrupts/diagnostics/status information | |
| Diagnostics function | Yes |
| Diagnoses | |
|
● Overrange
|
Yes |
|
● Wire-break in actuator cable
|
Yes |
| Diagnostics indication LED | |
|
● Group error SF (red)
|
Yes |
|
● Channel fault indicator F (red)
|
Yes |
| Ex(i) characteristics | |
| Module for Ex(i) protection | Yes |
| Maximum values of output circuits (per channel) | |
|
● Co (permissible external capacity), max.
|
850 nF |
|
● Io (short-circuit current), max.
|
70 mA |
|
● Lo (permissible external inductivity), max.
|
6.6 mH |
|
● Po (power of load), max.
|
440 mW |
|
● Uo (output no-load voltage), max.
|
14 V |
| Potential separation | |
| Potential separation analog outputs | |
|
● between the channels
|
Yes |
|
● between the channels and backplane bus
|
Yes |
|
● Between the channels and load voltage L+
|
Yes |
| Standards, approvals, certificates | |
| Use in hazardous areas | |
|
● Type of protection acc. to EN 50020 (CENELEC)
|
[EEx ib] IIC |
|
● Type of protection acc. to FM
|
Class I, Division 2, Group A, B, C, D T4 |
|
● Test number PTB
|
Ex-96.D.2026X |
| Ambient conditions | |
| Ambient temperature during operation | |
|
● max.
|
60 °C |
| Connection method | |
| required front connector | 20-pin |
| Dimensions | |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 120 mm |
| Weights | |
| Weight, approx. | 280 g |