| Article number | 6GK7443-1EX30-0XE0 |
| Product type designation | CP 443-1 |
| Transfer rate | |
| Transfer rate | |
|
● at the 1st interface
|
10 … 100 Mbit/s |
| Interfaces | |
| Number of interfaces acc. To
Industrial Ethernet |
2 |
| Number of electrical connections | |
|
● at the 1st interface acc. to Industrial Ethernet
|
2 |
| Type of electrical connection | |
|
● at the 1st interface acc. to Industrial Ethernet
|
RJ45 port |
| design of the removable storage C-PLUG | No |
| Supply voltage, current
consumption, power loss |
|
| Type of voltage of the supply voltage | DC |
| Supply voltage 1 from backplane bus | 5 V |
| Relative symmetrical tolerance at DC | |
|
● at 5 V
|
5 % |
| Consumed current | |
|
● from backplane bus at DC at 5 V typical
|
1.4 A |
| Power loss [W] | 7.25 W |
| Ambient conditions | |
| Ambient temperature | |
|
● during operation
|
0 … 60 °C |
|
● during storage
|
-40 … +70 °C |
|
● during transport
|
-40 … +70 °C |
| Relative humidity | |
|
● at 25 °C without condensation during operation maximum
|
95 % |
| Protection class IP | IP20 |
| Design, dimensions and weights | |
| Module format | Compact module S7-400 single width |
| Width | 25 mm |
| Height | 290 mm |
| Depth | 210 mm |
| Net weight | 0.7 kg |
| Product features, product
functions, product components general |
|
| Number of units | |
|
● per CPU maximum
|
14 |
|
● Note
|
max. 4 as PN IO ctrl. |
| Performance data open communication | |
| Number of possible
connections for open communication by means of SEND/RECEIVE blocks maximum |
64 |
| Amount of data | |
|
● as user data per ISO connection for open communication by means of SEND/RECEIVE blocks maximum
|
8 Kibyte |
|
● as user data per ISO on TCP connection for open communication by means of SEND/RECEIVE blocks maximum
|
8 Kibyte |
|
● as user data per TCP connection for open communication by means of SEND/RECEIVE blocks maximum
|
8 Kibyte |
|
● as user data per UDP connection for open IE communication by means of SEND/RECEIVE blocks maximum
|
2 Kibyte |
| Number of possible
connections for open communication |
|
|
● by means of T blocks maximum
|
64 |
| Amount of data | |
|
● as user data per ISO on TCP connection for open communication by means of T blocks maximum
|
1 452 byte |
| Performance data S7 communication | |
| Number of possible connections
for S7 communication |
|
|
● maximum
|
128; when using several CPUs |
|
● with PG connections maximum
|
2 |
| Performance data
multi-protocol mode |
|
| Number of active connections
with multi-protocol mode |
128 |
| Performance data PROFINET
communication as PN IO controller |
|
| Product function PROFINET
IO controller |
Yes |
| Number of PN IO devices on
PROFINET IO controller usable total |
128 |
| Number of PN IO IRT
devices on PROFINET IO controller usable |
64 |
| Number of external PN IO
lines with PROFINET per rack |
4 |
| Amount of data | |
|
● as user data for input variables as PROFINET IO controller maximum
|
4 Kibyte |
|
● as user data for input variables as PROFINET IO controller maximum
|
4 Kibyte |
|
● as user data for input variables per PN IO device as PROFINET IO controller maximum
|
1 433 byte |
|
● as user data for output variables per PN IO device as PROFINET IO controller maximum
|
1 433 byte |
|
● as user data for input variables per PN IO device for each sub-module as PROFINET IO controller maximum
|
240 byte |
|
● as user data for output variables per PN IO device for each sub-module as PROFINET IO controller maximum
|
240 byte |
| Product functions management,
configuration, engineering |
|
| Product function MIB support | Yes |
| Protocol is supported | |
|
● SNMP v1
|
Yes |
|
● DCP
|
Yes |
|
● LLDP
|
Yes |
| Configuration software | |
|
● required
|
STEP 7 V5.5 SP3 or higher / STEP 7 Professional V12 (TIA Portal) or higher |
| Product functions Diagnostics | |
| Product function Web-based diagnostics | Yes |
| Product functions Switch | |
| Product feature Switch | Yes |
| Product function | |
|
● switch-managed
|
No |
|
● with IRT PROFINET IO switch
|
Yes |
|
● Configuration with STEP 7
|
Yes |
| Product functions redundancy | |
| Product function | |
|
● Ring redundancy
|
Yes |
|
● Redundancy manager
|
Yes |
| Protocol is supported Media
Redundancy Protocol (MRP) |
Yes |
| Product functions Security | |
| Product function | |
|
● password protection for Web applications
|
No |
|
● ACL – IP-based
|
Yes |
|
● ACL – IP-based for PLC/routing
|
No |
|
● switch-off of non-required services
|
Yes |
|
● Blocking of communication via physical ports
|
Yes |
|
● log file for unauthorized access
|
No |
| Product functions time | |
| Product function SICLOCK
support |
Yes |
| Product function
pass on time synchronization |
Yes |
| Protocol is supported | |
|
● NTP
|
Yes |