| Type | GXL-15 type | |||
| Type | Standard | Long sensing range (For mounting on non-magnetic body) (Note 2) |
||
| Type | Front sensing | Top sensing | Front sensing | Top sensing |
| Standard Model No. | GXL-15FU | GXL-15HU | GXL-15FLU | GXL-15HLU |
| CE marking directive compliance | EMC Directive, RoHS Directive | |||
| Max. operation distance (Note 3) | 5 mm 0.197 in ± 10% | 8 mm 0.315 in ± 10% | ||
| Stable sensing range (Note 3) | 0 to 4 mm 0 to 0.157 in |
0 to 6.4 mm 0 to 0.252 in |
||
| Standard sensing object | Iron sheet 20 x 20 x t 1 mm 0.787 x 0.787 x t 0.039 in |
Iron sheet 30 x 30 x t 1 mm 1.181 x 1.181 x t 0.039 in |
||
| Hysteresis | 20 % or less of operation distance (with standard sensing object) |
|||
| Repeatability | Along sensing axis, perpendicular to sensing axis: 0.04 mm 0.002 in or less | |||
| Supply voltage | 12 to 24 V DC ± 10 % Ripple P-P 10 % or less | |||
| Current consumption (Note 4) | 0.8 mA or less | |||
| Output | Non-contact DC 2-wire type ・Load current: 3 to 100 mA (Note 5) ・Residual voltage: 3 V or less (Note 6) |
|||
|
Utilization category |
DC-12 or DC-13 | |||
| Short-circuit protection | Incorporated | |||
| Max. response frequency | 1 kHz | |||
| Operation indicator | Normally closed type: Red LED (lights up when the output is ON) |
|||
| 2-color indicator | Normally open type: Lights up in green under stable sensing condition Lights up in red under unstable sensing condition |
|||
| Pollution degree | 3 (Industrial environment) | |||
| Protection | IP67 (IEC), IP67G (Note 7) | |||
| Ambient temperature | -25 to +70 ℃ -13 to +158 ℉, Storage: -30 to +80 ℃ -22 to +176 ℉ | |||
| Ambient humidity | 45 to 85 % RH, Storage: 35 to 95 % RH | |||
| Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | |||
| Insulation resistance | 50 MΩ, or more, with 250 V DC megger between all supply terminals connected together and enclosure | |||
| Vibration resistance | 10 to 55 Hz frequency, 1.5 mm 0.059 in double amplitude in X, Y and Z directions for two hours each | |||
| Shock resistance | 1,000 m/s2 acceleration (100 G approx.) in X, Y and Z directions three times each | |||
| Material | Enclosure: PBT, Indicator part: Polyarylate | Enclosure: PET Indicator part: Polyarylate |
Enclosure: PBT Indicator part: Polyarylate |
Enclosure: PET Indicator part: Polyarylate |
| Cable (Note 8) | 0.2 mm2 2-core oil, heat and cold resistant cable, 1 m 3.281 ft long | |||
| Cable extension | Extension up to total 50 m 164.042 ft is possible with 0.3 mm2, or more, cable. | |||
| Weight | Net weight: 20 g approx. | |||
| Accessories | – | MS-A15F (Aluminum sheet): 1 pc. |
MS-A15H (Aluminum sheet): 1 pc. |
|