| Article number | 6GK7542-5DX00-0XE0 |
| Product type designation | CM 1542-5 |
| Transfer rate | |
| Transfer rate | |
|
● at the 1st interface acc. to PROFIBUS
|
9.6 kbit/s … 12 Mbit/s |
| Interfaces | |
| Number of interfaces acc. to Industrial Ethernet | 0 |
| Number of electrical connections | |
|
● at the 1st interface acc. to PROFIBUS
|
1 |
| Type of electrical connection | |
|
● at the 1st interface acc. to PROFIBUS
|
9-pin Sub-D socket (RS485) |
| Supply voltage, current consumption, power loss | |
| Type of voltage of the supply voltage | DC |
| Supply voltage 1 from backplane bus | 15 V |
| Relative symmetrical tolerance at DC | |
|
● at 15 V
|
3 % |
| Consumed current | |
|
● from backplane bus at DC at 15 V typical
|
0.2 A |
| Power loss [W] | 3 W |
| Ambient conditions | |
| Ambient temperature | |
|
● for vertical installation during operation
|
0 … 40 °C |
|
● for horizontally arranged busbars during operation
|
0 … 60 °C |
|
● during storage
|
-40 … +70 °C |
|
● during transport
|
-40 … +70 °C |
| Relative humidity | |
|
● at 25 °C without condensation during operation maximum
|
95 % |
| Protection class IP | IP20 |
| Design, dimensions and weights | |
| Module format | Compact module S7-1500 single width |
| Width | 35 mm |
| Height | 142 mm |
| Depth | 129 mm |
| Net weight | 0.4 kg |
| Mounting type | |
|
● S7-1500 rail mounting
|
Yes |
| Product features, product functions, product components general | |
| Number of units | |
|
● per CPU maximum
|
8 |
|
● Note
|
depending on CPU type |
| Performance data open communication | |
| Number of possible connections for open communication by means of SEND/RECEIVE blocks maximum | 30 |
| Amount of data | |
|
● as user data per connection for open communication by means of SEND/RECEIVE blocks maximum
|
240 byte |
| Performance data PROFIBUS DP | |
| Service as DP master | |
|
● DPV1
|
Yes |
| Number of DP slaves | |
|
● on DP master usable
|
125 |
| Amount of data | |
|
● of the address area of the inputs as DP master total
|
8 192 byte |
|
● of the address area of the outputs as DP master total
|
8 192 byte |
|
● of the address area of the inputs per DP slave
|
244 byte |
|
● of the address area of the outputs per DP slave
|
244 byte |
| Service as DP slave | |
|
● DPV0
|
Yes |
|
● DPV1
|
Yes |
| Amount of data | |
|
● of the address area of the inputs as DP slave total
|
240 byte |
|
● of the address area of the outputs as DP slave total
|
240 byte |
| Performance data S7 communication | |
| Number of possible connections for S7 communication | |
|
● maximum
|
48; depending on the system upper limit |
| Performance data multi-protocol mode | |
| Number of active connections with multi-protocol mode | 48 |
| Performance data telecontrol | |
| Protocol is supported | |
|
● TCP/IP
|
No |
| Product functions management, configuration, engineering | |
| Configuration software | |
|
● required
|
STEP 7 Professional V12 (TIA Portal) or higher |
| Identification & maintenance function | |
|
● I&M0 – device-specific information
|
Yes |
|
● I&M1 – higher-level designation/location designation
|
Yes |
| Product functions Diagnostics | |
| Product function Web-based diagnostics | Yes; via S7-1500 CPU |
| Product functions time | |
| Product function pass on time synchronization | Yes |