| Item | G9EC-1(-B) |
| Contact resistance (See note 2.) | 30 mW max. (0.2 mW typical) |
| Contact voltage drop | 0.1 V max. (for a carry current of 200 A) |
| Operate time | 50 ms max. |
| Release time | 30 ms max. |
| Between coil and contacts | 1,000 MW min. |
| Between contacts of the same polarity | 1,000 MW min. |
| Between coil and contacts | 2,500 VAC, 1 min |
| Between contacts of the same polarity | 2,500 VAC, 1 min |
| Impulse withstand voltage (See note 4.) | 4,500 V |
| Destruction | 10 to 55 to 10 Hz 0.75-mm single amplitude (Acceleration: 2.94 to 88.9 m/s2) |
| Malfunction | 10 to 55 to 10 Hz 0.75-mm single amplitude (Acceleration: 2.94 to 88.9 m/s2) |
| Destruction | 490 m/s2 |
| Malfunction | 196 m/s2 |
| Mechanical endurance (See note 5.) | 200,000 operations min. |
| Electrical endurance (resistive load) (See note 6.) | 400 VDC, 200 A, 3,000 operations min. |
| Short-time carry current | 300 A (15 min) |
| Maximum interruption current | 1,000 A at 400 VDC (10 times) |
| Overload interruption | 700 A at 400 VDC (40 times min.) |
| Reverse polarity interruption | –200 A at 200 VDC (1,000 times min.) |
| Ambient operating temperature | –40 to 50°C (with no icing or condensation) |
| Ambient operating humidity | 5% to 85% |
| Weight | Approx. 560 g |