| Safety integrity level | SIL3 (IEC 61508)
SILCL3 (EN 62061) |
| Category | Category 4 (EN ISO 13849) |
| Performance level | PL e (EN ISO 13849) |
| B10d parameter | 1.26 x 106 switching cycles (AC-15, 230 V, I = 1.5 A)
5.9 x 106 switching cycles (AC-15, 230 V, I = 0.75 A) 4.35 x 105 switching cycles (DC-13, 24 V, I = 2.5 A) 1 x 107 switching cycles (DC-13, 24 V, I = 0.63 A) |
| PFHD (mean probability of a dangerous failure per hour) | 3.0 x 10-8 (EN ISO 13849) |
| TM (mission time) | 20 years (EN ISO 13849) |
| Stop category | 0 (EN 60204-1) |
| Connection type | Fixed screw terminals |
| Number of enabling current paths (N/O) | 2, relevant for safety |
| Residual ripple | ≤ 2.4 Vpp 1) |
| Power consumption | (≤ 4.6 VA (AC))
(≤ 2.1 W (DC)) |
| Overvoltage category | II |
| Rated insulation voltage Ui | 300 V AC |
| Rated impulse withstand voltage Uimp | 4 kV |
| Test voltage | 2 kV (50 Hz) (EN 60439-1) |
| Control voltage | 22 V DC (≥ 17.4 V DC) |
| Control current | 40 mA … 100 mA |
| Short-circuit current | ≤ 300 mA, between S33 / S11 and S21 |
| Short-circuit protection | Electronic fuse |
| Galvanized decoupling | – (between A1, A2 and S11, S21, S33) |