| Article number | 6ES7232-4HA30-0XB0 |
| Signal Board SB 1232, 1 AO | |
| General information | |
| Product type designation | SB 1232, AQ 1×12 bit |
| Input current | |
| from backplane bus 5 V DC, typ. | 15 mA |
| Output voltage | |
| Power supply to the transmitters | |
| ·
● Supply current, max. · |
25 mA |
| Power loss | |
| Power loss, typ. | 1.5 W |
| Analog inputs | |
| Number of analog inputs | 0 |
| Analog outputs | |
| Number of analog outputs | 1 |
| Cycle time (all channels) max. | Voltage: 300 μS (R), 750 μS (1 uF) Current: 600 ms (1 mH); 2 ms (10 mH) |
| Output ranges, voltage | |
| ·
● -10 V to +10 V · |
Yes |
| Output ranges, current | |
| ·
● 0 to 20 mA · |
Yes |
| Load impedance (in rated range of output) | |
| ·
● with voltage outputs, min. · |
1 000 Ω |
| ·
● with current outputs, max. · |
600 Ω |
| Cable length | |
| ·
● shielded, max. · |
100 m; shielded, twisted pair |
| Analog value generation for the outputs | |
| Conversion principle | Differential |
| Integration and conversion time/resolution per channel | |
| ·
● Resolution with overrange (bit including sign), max. · |
12 bit |
| Errors/accuracies | |
| Temperature error (relative to output range), (+/-) | 25 °C ±0.5%, to 55 °C ±1% |
| Interrupts/diagnostics/status information | |
| Alarms | Yes |
| Diagnostics function | Yes |
| Diagnostics indication LED | |
| ·
● for status of the outputs · |
Yes |
| Standards, approvals, certificates | |
| CE mark | Yes |
| CSA approval | Yes |
| UL approval | Yes |
| cULus | Yes |
| FM approval | Yes |
| RCM (formerly C-TICK) | Yes |
| KC approval | Yes |
| Marine approval | Yes |
| Ambient conditions | |
| Free fall | |
| ·
● Fall height, max. · |
0.3 m; five times, in product package |
| Ambient temperature during operation | |
| ·
● min. · |
-20 °C |
| ·
● max. · |
60 °C |
| ·
● horizontal installation, min. · |
-20 °C |
| ·
● horizontal installation, max. · |
60 °C |
| ·
● vertical installation, min. · |
-20 °C |
| ·
● vertical installation, max. · |
50 °C |
| Ambient temperature during storage/transportation | |
| ·
● min. · |
-40 °C |
| ·
● max. · |
70 °C |
| Air pressure acc. to IEC 60068-2-13 | |
| ·
● Storage/transport, min. · |
660 hPa |
| ·
● Storage/transport, max. · |
1 080 hPa |
| Relative humidity | |
| ·
● Operation at 25 ℃ without condensation, max. · |
95 % |
| Pollutant concentrations | |
| ·
● SO2 at RH < 60% without condensation · |
S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free |
| Mechanics/material | |
| Enclosure material (front) | |
| ·
● Plastic · |
Yes |
| Dimensions | |
| Width | 38 mm |
| Height | 62 mm |
| Depth | 21 mm |
| Weights | |
| Weight, approx. | 40 g |